DV-300 Adjustable Speed Drives

——— FUNCTION DESCRIPTION ———

6

69

Select input XX

Selection of the parameter to be assigned its value via an analog input. The following

assignments are possible:

OFF

Jog reference

1)

Speed ref 1

1)

Speed ref 2

1)

Ramp ref 1

1)

Ramp ref 2

1)

T current ref 1

2)

T current ref 2

2)

Adap reference

1)

T current limit

2)

0

1

2

3

4

5

6

7

8

9

T current lim +

2)

T current lim -

2)

Pad 0

3)

Pad 1

3)

Pad 2

3)

Pad 3

3)

Load comp

PID offset 0

4)

PI central v3

4)

PID feed-back

4)

10

11

12

13

14

15

19

21

22

23

Flux current max

Out vlt level

Speed ratio

5)

Tension red

Tension ref

Preset 3

Brake Ref *

25

26

28

29

30

31

32

* Reference for the Torque proving parameter setting.

An in xx target

Assign the analog input xx sampling. If assigned, the sampled value is copied into the

parameter programmed on the analog input. If not assigned, the programmed parameter

takes the value preset via keypad or RS485 or BUS, before to assign an analog input.

Exception are the “PAD” parameters, where the last value on the analog input is stored

when An in XX target = not assigned is executed.

Input XX type

Selection of input type (voltage or current input)

Jumpers on the regulator card of the DV-300 should be fitted or removed according to

the input signal used. The inputs of the device are factory set for voltage signls.

Analog Input

Input Signal

-10 V ... + 10 V

0 - 10 V

0 - 20 mA
4 - 20 mA

Analog input 1

S9 = OFF

S9 = ON

Analog input 2

S10 = OFF

S10 = ON

Analog input 3

S11 = OFF

S11 = ON

GD6185g

ON

Jumper fitted

OFF

Jumper not fitted

10 V...+10 V

A voltage of max ±10 V is connected to the analog input concerned.

If the signal is used as a reference value, a polarity reversal can

be used to reverse the rotation direction of the drive (only with

6KDV3 ... Q4 converters). The 6KDV3 ... Q2 converters accept

as speed reference only positive references. Negative references

are not accepted and the drive does not start.

0-10V, 0-20mA

A voltage of max. 10 V or a current signal of 0...20 mA is

connected to the analog input concerned. The signal must be

positive. If the signal is used as a reference value for 6KDV3...

Q4 converters, the rotation direction can be reversed via the

Input XX sign + and Input XX sign - parameters.

4-20 mA

A current signal of 4...20 mA is connected to the analog input

concerned. The signal must be positive. If the signal is used as a

reference value for 6KDV3 ... Q4 converters, the drive rotation

direction can be reversed via the Input XX sign + and Input

XX sign - parameters.

Input XX sign

Selection of rotation direction when operated via the serial interface or bus for the tet-

raquadrant 6KDV3 ... Q4 converters.

Input XX sign +

Selection of “Clockwise” rotation when operated via the terminal strip for the 6KDV3...4B

converters, when the reference value is only given with one polarity.

High

Clockwise selected

Low

Clockwise not selected