13 additional speed functions (add speed funct), 1 auto capture, 2 adptive spd reg – GE Industrial Solutions DV-300 DC Drive Users Manual User Manual

Page 209: 1 auto capture 6.13.2 adptive spd reg

Advertising
background image

DV-300 Adjustable Speed Drives

——— FUNCTION DESCRIPTION ———

6

81

6.13 ADDITIONAL SpEED FuNCTIONS (ADD SpEED FuNCT)

6.13.1 Auto capture

ADD SPEED FUNCT

[388]

Auto capture

The auto capture function enables the converter to engage a unning motor.

Parameter description

No.

Value

Standard

Configuration

min

max

Factory

American

Factory

European

Auto capture

ON (1)

OFF (0)

388

OFF (0)

OFF (0)

*

* This function can be assigned to one of the programmable digital inputs.

Auto capture

ON

When the converter is switched on, the speed of the motor is

measured and the ramp output is set accordingly. The drive

then runs to the set reference value.

OFF

When the converter is switched on, the ramp starts from zero.

Main uses:

Connection to a motor that is already running due to its load (e.g. in the case of

pumps, the flowing medium).

Reconnection after a fault alarm.

If the speed reference value is defined via the ramp, with Auto capture = ON, starting at a reference value cor-

responding to the motor speed.

n

ote

!

If the function is switched off, ensure that the motor is not turning when the converter is switched

on. If this is not the case, this may cause a harsh motor deceleration in current limit.

6.13.2 Adptive spd reg

ADD SPEED FUNCT

Adaptive spd reg

[181]

Enable spd adap

[182]

Select adap type

[183]

Adap reference [FF]

[1464]

Adap selector

[184]

Adap speed 1 [%]

[185]

Adap speed 2 [%]

[186]

Adap joint 1 [%]

[187]

Adap joint 2 [%]

[188]

Adap P gain 1 [%]

[189]

Adap I gain 1 [%]

[190]

Adap P gain 2 [%]

[191]

Adap I gain 2 [%]

[192]

Adap P gain 3 [%]

[193]

Adap I gain 3 [%]

[1462]

Adap P gain 4 [%]

[1463]

Adap I gain 4 [%]