——— FUNCTION DESCRIPTION ———

6

139

6.16.3.3 Feed - Forward

PID source

[786]

PID source

[787]

PID source gain

[758]

Feed-fwd PID

Parameter description

No.

Value

Standard

Configuration

min

max

Factory

American

Factory

European

PID source

786

0

65535

0

0

PID source gain

787

-100.000 +100.00

1.000

1.000

Feed-fwd PID

758

-10000

+10000

0

0

*

* This parameter can be set on an analog programmable input..

When used , the feed-forward signal represents the main reference of the regulator. Inside the regulator it will

be attenuated or amplified by the PID function and sent to the output as reference signal for the drive.

I/O Parameter

Parameter

Internal variable

LEGEND:

PID source

Gain

PID source gain

Feed-fwd PID

Figure 6.16.3.1: Feed-forward block description

PID source

Address of the parameter (Feed-forward value) containing the value which will be used

as PID source.

Number +2000H (8192 decimal) must be added to the parameter.

PID source gain

Multiplier of the input value to PID source.

Feed-fwd PID

Value of feed-forward

Through the parameter PID source, it is possible to select which point in the drive the feed-forward signal may

be sent. The selectable parameters are those indicated in the paragraph 10.4. “List of the high-priority param-

eters”. The measure units are those indicated in the notes at the end of this paragraph.

1. Programming example of the ramp output block (Parameter Ramp out) on PID source:

Menu OPTION

————> PID

————> PID source

————> PID source = 8305

The PID source must be set to the parameter number to which it will be associated, choosing it from paragraph

10.4. “List of high-priority parameters” (Ramp out has the decimal number 113).

To obtain the value, it must be added to the decimal value 8192 (fixed offset):
8192 + 113 = 8305.
If you need to set the feed-forward on analog input, given that they are not directly inserted in the ‘high-priority

parameters’, it is necessary to pass through a PAD 0.....PAD 15 parameter.