——— WIRING PROCEDURES ———

4

8

Table 4.4.4: Jumpers on the R-TPD32-GE card

Designation

Function

Factory

S4

Matching of the input voltage of the tachogenerator reaction,
see table 4.4.3

S5,S6

Adaptation of the speed feedback type:

B

Pos. A

Sinusoidal encoder

Pos. B

Tachogenerator

Any position: digital encoder, armature feedback

S9

Adaptation to the signal of the analog input Input 1 (terminals 1 and 2)

OFF

ON

0 ... 20 mA / 4 ... 20 mA

OFF

0 ... 10V / -10 ... +10V

S10

Adaptation to the signal of the analog input Input 2 (terminal 3 and 4)

OFF

ON

0 ... 20 mA / 4 ... 20 mA

OFF

0 ... 10V / -10 ... +10V

S11

Adaptation to the signal of the analog Input 3 (terminals 5 and 6)

OFF

ON

0 ... 20 mA / 4 ... 20 mA

OFF

0 ... 10V / -10 ... +10V

S12 / S13

Terminating resistor for the serial interface RS485

OFF

ON

Interface terminated with resistor

OFF

Interface not terminated

S14

Field current resistors setting, see table 2.4.3.2

S15

Adaptation of the regulation card to the device type, see table 4.4.2

S18 / S19

Selection of the internal/external supply of the RS485 serial interface

OFF

OFF

Serial interface supplied from the outside (PIN 5 and 9) and
galvanic divided form the regulation section.

ON

Serial interface supplied from the inside and connected to the
potential reference point of the regulation. PIN 5 and 9 are used to
supply the adaptor of the serial interface (for use of 6KDV300PIU).

S20

Monitoring of the C channel of the digitall encoder on connector XE2

OFF

ON

C-channel monitored

OFF

C-channel not monitored

S21 / S22 / S23

Encoder supply voltage selection

OFF

ON

5 V encoder supply voltage

OFF

15...30 V encoder supply voltage

GD0160g

ON Mounted Jumpers

OFF Non mounted Jumpers

Table 4.4.5: Test points on Regulator card

Designation

Function

Designation

Function

XY20

Monitoring (± 10VDC) of the Se-

lect output parameters setting.

(Using this test point set all the Select output

1,2,3,4 to the variable that has to be measured).

XY17

Output current signal

(0.61 V =Nominal Drive output current)

XY10

Reference point

XY18

Reference point