7 output reference – GE Industrial Solutions DV-300 DC Drive Users Manual User Manual

Page 277

Advertising
background image

DV-300 Adjustable Speed Drives

——— FUNCTION DESCRIPTION ———

6

149

6.16.3.7 Output reference

Figure 6.16.3.5: Output reference block description

PD control

[772]

PID out sign PID

[774]

PID output

Parameter description

No.

Value

Standard

Configuration

min

max

Factory

American

Factory

European

PID out sign PID

Positive (0)

Bipolar (1)

772

0

1

1

1

PID output

774

-10000

+10000

0

0

*

* This parameter can be set on an analogue programmable output.

PID out. sign PID

Through this parameter it is possible to set the output of the regulator to be either bipolar

or simply positive (clamp of negative side).

PID output

Display of regulator output. It is possible to program this parameter to an analog output,

in order to perform a reference cascade in multidrive systems.