——— FUNCTION DESCRIPTION ———

6

4

6.1.1 Enable drive

DRIVE STATUS

START UP

TUNING

MONITOR

[314]

Enable drive

Parameter

No.

Value

Standard

Configuration

min

max

Factory

American

Factory

European

Enable drive

Enabled

Disabled

314

0

1

Disabled

Disabled

Terminal 12

+15 ... 30 V

0 V

The Enable drive command activates the DV-300 Drive.
An auxiliary contact on the AC Input contactor may be wired in the Drive enable (terminal 12).
When the Enable drive=disable and terminal 12 = 0V, no other control commands (e.g. Jog +, Jog - or Start)

are accepted.
Removal of the Enable drive command (Enable drive=disable) while the drive is running causes the motor

coasting to stop. Neither electrical braking nor controlled stopping of the motor within a prescribed time during

the run down are possible. The actuation of the Drive is disabled.
When operated via the keypad the Enable drive command is provided in the DRIVE STATUS, START UP,

TUNING and MONITOR menu.
Using Enable drive command from keypad (mains command=Digital), active voltage level is also required

on terminal 12.
Using Enable drive command from terminal 12 set “Main command=terminals”.
Enable drive in the menu is read only parameter.