2 basic start up menus, Drive status, Start up – GE Industrial Solutions DV-300 DC Drive Users Manual User Manual

Page 136: First basic setting, Motor data

Advertising
background image

GEI-100332Ga

——— FUNCTION DESCRIPTION ———

6

8

6.2 BASIC START up MENuS

The following DRIVE STATUS, START UP and TUNING allow a basic commissioning of the drive.

n

ote

!

The parameters in these menus are available in other menus.

See Start up procedure on chapter 5.4 for commissioning information.

DRIVE STATuS

Menu displayed at power up.
Status parameters of the drive are available and Ramp ref 1 parameter for basic speed reference with ramp

time.

START up

In this menu the start up sequencing is available.

First basic setting

Speed base value

Speed base value is defined by the unit in the factor function specified. It is the reference

value for all the speed reference values (reference values, adaptive speed regulation)

given as a percentage, and corresponds to 100% of the speed. Changing this parameter is

only possible when the drive is disabled (Enable drive=Disable). The speed base value

does not define the maximum possible speed, which in some cases can be formed from

the addition of several reference values. This is defined with Speed max amount.

Nom flux curr

Drive field current value.

Speed-0 f weak

Enables the field economy at zero speed.

Acc / Dec ...

Acceleration and deceleration ramp time setting on the speed reference.(see chapter

6.6.1 for more details).

Motor data

Motor plate data:

Motor nom flux

Motor field current in Amps.

Flux reg mode

Field regulator mode.

Full load curr

Nominal motor current in Amps

Motor max speed

Maximum motor speed value

Max out voltage

Maximum armature voltage value

Flux weak speed

Motor max speed percentage where the flux weakening range starts. (Crossover

point)