2.6 WATT LOSS

The power dissipation on the converter side depends on the AC input voltage. The values of the dissipated pow-

ers stated in the following table refer to the functioning with rated current.

n

ote

!

The mounting should take into consideration a free space above and below the device of at

least 6 inches (150 mm). (Air circulation).

Starting from the type 560 / 770 A (American / European), the fans must be supplied from the outside with a

single-phase voltage of 230V 50/60 Hz (terminals U3 & V3).

American

European

Power loss

[W]

Fans

Enclosure

Voltage

Pv[V]

Rated current

[A]

Air capacity

[m

3

/h]

ventilation area

[mm

2

]

[in.

2

]

6KDV3017... 6KDV3020...

131

-

-

-

2 x 5100

2 x 7.91

6KDV3035... 6KDV3040...

186

-

-

-

2 x 5100

2 x 7.91

6KDV3056... 6KDV3070...

254

Internal power supply

80

2 x 5100

2 x 7.91

6KDV3088... 6KDV3110...

408

160

2 x 11300

2 x 17.53

6KDV3112... 6KDV3140...

476

160

2 x 11300

2 x 17.53

6KDV3148... 6KDV3185...

553

160

2 x 11300

2 x 17.53

6KDV3224... 6KDV3280...

781

320

2 x 22600

2 x 35.06

6KDV3280... 6KDV3350...

939

320

2 x 22600

2 x 35.06

6KDV3336... 6KDV3420...

1038

320

2 x 22600

2 x 35.06

6KDV3400... 6KDV3500...

1248

320

2 x 22600

2 x 35.06

6KDV3450... 6KDV3650...

1693

680

2 x 35400

2 x 54.91

6KDV3560... 6KDV3770...

2143

230

0.75

1050

2 x 53100

2 x 82.37

6KDV3800... 6KDV310H...

2590

230

0.75

1050

2 x 53100

2 x 82.37

6KDV3850...

2590

230

0.75

1050

2 x 53100

2 x 82.37

GD0100g

Table 2.6.1: Power Dissipation

*

When the Drive is mounted in a cabinet, door filters are required to meet pollution degree II ratings for UL.