GEI-100332Ga

——— FUNCTION DESCRIPTION ———

6

34

Fwd-Rev spd tune

Direction of motor shaft rotation for the speed self tune test (Forward or Reverse; For-

ward is clock-wise as seen from shaft drive end).

Test T curr lim

Torque current limit applied during Speed self tune test.

Start

Start-up speed self tune.

Inertia

Inertia value in Kg*m

2

(1 Kg*m

2

= 23.76 lb*ft

2

).

Inertia Nw

New Inertia value in Kg*m

2

identified during the speed self tune procedure.

Friction

Friction value (or Loss compensation) in N*m (1 N*m = 0.738 lb*ft).

Friction Nw

New Friction value (or Loss compensation) in N*m identified during the speed self tune

procedure.

Speed P

Proportional coefficient of the speed regulator in percentage.

Speed P Nw

New value of Proportional coefficient of the speed regulator in percentage computed

during the speed self tune procedure.

Speed I

Integral coefficient of the speed regulator in percentage.

Speed I Nw

New value of Integral coefficient of the speed regulator in percentage computed during

the speed self tune procedure.

Take val

Acquire the parameters after the speed self tune procedure (overwrite current values).

Note!

This is not a permanent save. Go to “Save parameters” command.

6.7.2 Spd zero logic

0

t

&

&

&

>=

>
=

&

>=

Lock speed I

Lock speed I

Ref 0 level

Speed zero

Speed

Ramp ref / Speed ref

T

T

T

Spd=0 P gain

10 %

Ref 0 level

10 rpm

Speed zero delay

100 ms

Enable spd=0 I

Enable spd=0 P

Enable spd=0 R

Figure 6.7.2.1: Speed zero logic

SPEED REGULAT

Spd zero logic

[123]

Enable spd=0 I

[124]

Enable spd=0 R

[125]

Enable spd=0 P

[126]

Spd=0 P gain [%]

[106]

Ref 0 level [FF]

The speed zero logic determines the behavior of the drive when the motor shaft is at a stop.