DV-300 Adjustable Speed Drives

——— WIRING PROCEDURES ———

4

19

Coil Suppressor

AC Input Contactor
K1M

ENABLE
K1MX

Drive OK

Contact closes
with power ON
FAN 560A and
above only

START
K2

FAST STOP

Drive OK

Reset

115 VAC from CPT

fed from AC incoming

START
PB

START
K2

FAN power
OK (Q1)

STOP
PB

85

86

FAST STOP
K0

Drive Healthy

picks up if OK

SNF

P.B.
latched on push, pull to reset
after the process has stopped

H

N

EXTERNAL
ESTOPS

System Not Fault

SNF

SNF

EXTERNAL
RUN
PERMISSIVES

T.D.A.D. *

- Time delay after de energization -
Set greater than the maximum
decel ramp time.

K1MX

K2

K0

SNF

19

15

19

14

19

13

19

12

+24V

+24V

+24V

+24V

EXT
FAULT

FAST
STOP

START

ENABLE

75

76

Operation set by parameter [629]
RELAY 2 and parameter [626] stop mode

K1M AUX
(MA AUX)

81

82

Blown
Fuse

560A and
above only

DV-300
Relay 2

K2

Figure 4.8.2: Example for relay interface

n

ote

!

1 - ENABLE must remained energized during a normal STOP or FAST STOP for the DV-300

to decel on a ramp.

2 - ENABLE must be de energized to power up and to reset a fault or alarm.

3 - If the external fault input, or fast stop input, is unused, the unused input must

be tied to + 24V (terminal 19).

4 - EXTERNAL FAULT input, FAST STOP input, START input and ENABLE input

need picked up during LAN operation. Opening the input will cause labeled drive

reaction.

* - T.D.A.D. = Time Delay After De energization.