——— TROUBLESHOOTING ———

8

7

FAILURE

POSSIBLE CAUSES

The speed during acceleration with max. current is not linear

Reduce the Speed I and Speed P proportionally. If this does not lead to an improvement,

optimize the regulator (see chapter 5.3.6).

Speed oscillating

Check Speed P and Speed I parameter

If the operating point is in the field weak range, check the Fld reg P gain and Fld

reg I gain parameters and eventually Voltage P and Voltage I parameters.

Remedy: Optimize the regulator as previously described

Drive not reacting to adaptive speed regulation

Adaptive speed regulation not enabled. Enable spd adap = Enabled

Motor potentiometer function not executed

Function not enabled. Enable motor pot = Enabled

With operation via the terminal strip: Motor pot up and/or Motor pot down were not

assigned to a digital input

Jog operation not possible

A start command is still present

Function not enabled. Enable jog = Enabled

With operation via terminal strip: Jog + and/or Jog - were not assigned to a digital input.

Internal speed reference values not carried out

Function not enabled. Enab multi spd = Enabled

With operation via terminal strip: Speed sel 0, Speed sel 1 and Speed sel 2 were not

assigned to a digital input.

Multi-Ramp function not reacting

Function not enabled. Enab multi rmp = Enabled

With operation via terminal strip: Ramp sel 0 and Ramp sel 1 were not assigned to a

digital input

Overload not possible

Function not enabled. Enable overload = Enabled