GEI-100332Ga

——— FUNCTION DESCRIPTION ———

6

70

Input XX sign -

Selection of “Counter-clockwise” rotation when operated via the terminal strip for the

6KDV3 ... Q4 converters, when the reference value is only

given with one polarity.

High

Counterclockwise selected

Low

Counterclockwise not selected

If both Input XX sign+ and Input XX sign- are 0 or 1 the reference value is zero.

Scale input XX

Scaling of the corresponding analog input

1)

With a scaling factor of 1 and a Tune value inp XX = 1, 10 V or 20 mA on the

input correspond to the Speed base value.

2)

With a scaling factor of 1 and a Tune value inp XX = 1, 10 V or 20 mA on the

input correspond to max possible current.

3)

With a scaling factor of 1, 10V or 20 mA in the input correspond to the Pad value of 2047.

4)

For the max. full scale values, refer to paragraph 6.16.3 PID function

5)

With a scaling factor of 1.0 and Tune value inp XX=1, 10V or 20mA correspond

to Speed ratio = 20000.

Tune value inp XX

Fine tuning of the input when the max. signal does not exactly correspond to the rated

value. Example see below.

Auto tune inp XX

Automatic fine tuning of the input. If this command is given, Tune value inp XX is auto-

matically selected so that the input signal present corresponds to the max. variable value,

such as the Speed base value. Two conditions are necessary for automatic fine tuning:

Input voltage greater than 1 V or input current greater than 2 mA

Positive polarity. The value found is automatically set for the other direction for

the 6KDV3 ... Q4 converters.

Note: The automatically calculated value can, if necessary, be modified manually

via Tune value inp XX.

Offset inp XX

If the analog signal has an offset or if the variable assigned to the input already has a value

although there is no input signal present, this can be compensated via the Offset inp XX.

The converter is factory set so that analog values as +10V/-10V.
With field bus operation (Option), the Input XX sign parameter specifies the sign for the rotation direction.
If a parameter is already internally assigned (e.g. if Speed ref 1 is automatically connected with the ramp output when

the ramp is enabled), it will no longer appear in the list of parameters that can be assigned to an analog input.
The Input XX sign + and Input sign - parameters cannot be addressed via the serial interface.

Example 1:

The speed reference value of a drive is defined with an external voltage of 5V. With this

value the drive should reach the max. allowed speed (set via Sped base value).

As parameter Scale input XX the scaling factor 2 is entered (10V : 5V)

Example 2:

An external analog reference reaches only max. 9.8V instead of 10V.

As parameter Tune value inp XX 1.020 is entered (10V : 9.8V).

The same result would have been obtained via the Auto tune inp XX function. The

appropriate parameters would have to be entered in the menu of the keypad. The maxi-

mum possible analog value (in this case 9.8 V) would have to be present at the terminal

with a positive polarity. The keypad will adjust the “Tune value” automatically if the

ENTER key is pressed.