DV-300 Adjustable Speed Drives

——— WIRING PROCEDURES ———

4

13

n

ote

!

A connection point to point can be done using “6KCV300CTI” option interface (S18 and

S19 mounted). For multidrop connection (two or more drive), an external power supply is

necessary (pin 5 / 0V and pin 9 / +5V). Pins 6 and 8 are reserved for use with the “6KCV-

300CTI” interface card.

When connecting the serial interface ensure that:

- only shielded cables are used

- power cables and control cables for contactors/relays are routed separately.

4.5.2 RS485 serial interface connector description

Table 4.5.2.1: Description of the XS connector for the RS485 serial interface

Designation*

Function

I/O

Elec. Interface

PIN 1

Internal use

PIN 2

Internal use

PIN 3

RxA/TxA

I/O

RS485

PIN 4

Internal use

PIN 5

0 V (reference point 5V)

Power supply

PIN 6

Internal use

PIN 7

RxB/TxB

I/O

RS485

PIN 8

Internal use

PIN 9

+5V

Power supply

GD0230g

*

9-pole socket connector, fitted on device. A plug connector acc. DIN 41 652 is required for the connection

The pin 5 and 9 function depends on the position of the jumpers S18 and S19

S18 and S19 in position OFF

The serial interface is galvanic separated from the regulator section.

The serial interface power supply is provided from the outside via the PIN

5 (0V) and PIN 9 (+5V) of the XS connector (default factory setting).

S18 and S19 in position ON

The serial interface has the same potential reference point as the regula-

tor. The PIN 5 and 9 can be used to supply the adaptor of the RS 232 to

RS 485 serial interface that can be purchased from the General Electric

Company. They can not be used for any other purpose!

4.6 INpuT/OuTpuT ExpANSION CARD 6KCV300TBO

The input/output expansion card 6KCV300TBO can be fitted in a converter of the DV-300 Series. The card

provides analog outputs and digital inputs/outputs.
This option card, which is inserted on the XBB connector, is considered by the device as TBO “B”.