——— FUNCTION DESCRIPTION ———

6

46

6.11 CONFIGuRATION

6.11.1 Operating mode selection

CONFIGURATION

[252]

Main commands

[253]

Control mode

Parameter description

No.

Value

Standard

Configuration

min

max

Factory

American

Factory

European

Main commands

Terminals (0)

Digital (1)

252

0

1

Term.(0)

Term.(0)

-

Control mode

Local (0)

Bus (1)

253

0

1

Local (0)

Local (0)

-

Main commands

These commands specify from where the Enable drive, Start and Fast stop commands

are to be actuated.

Terminals

The above commands are actuated exclusively via the

terminal strip.

Digital

Commands must be selected both via the terminal strip and

via the digital channel (keypad or RS485 or bus, depending

on the Control mode). If, for example, a stop of the drive is

initiated by removing the Start command on terminal 13, both

the voltage on terminal 13 and the command via the digital

channel are necessary to restart the drive. This also applies to a

removal of the Fast stop command. If the Stop is initiated via

the digital channel, the digital command is sufficient to restart

the drive.

The control method through terminal commands (Terminals) is selectable only when

terminals 12 (Enable) and 13 (Start) are not supplied.

Carrying out the passage of the commands from Digital to Terminals with those terminals

supplied, it will appear the message “Change input”, signalling the wrong action.

Control mode

Defines whether the digital channel is the keypad/RS485 or a bus system (Option).

Local

The digital channel is the keypad or the RS485 serial interface

Bus

The digital channel is a bus system (Option)

The following tables show the operating modes possible.