DV-300 Adjustable Speed Drives

——— FUNCTION DESCRIPTION ———

6

195

6.17.5 Control logic

This chapter describes the most common logic sequences:
1.

Diameter initialization

2.

Initial phase

3.

Automatic switch

4.

Coil stop

5.

Jog function

Diameter initialization

This sequence is carried out before the starting of a winder/unwinder both with a coil initial phase when the line

is stopped and during an automatic switching.
The diameter value set in Roll diameter depends on the parameters Diam preset 0, 1, 2, 3 and on Diam preset sel.

If 2-4 different values of the starting diameter have been set, the selection has to be carried out via some

programmed digital inputs such as Diam preset sel 0 and Diam preset sel 1, or via the parameter Diam

preset sel.

If the value of the starting diameter is set via an analog input, set Diam preset sel = 3.

Enable the parameter Diam reset for a time longer than 20ms.

Reset the digital input status before the start.

Initial phase

This sequence is carried out in order to start the initial phase with a stopped line.

Torque winder En

Start (drive)

Diam reset

Figure 6.17.9: Initial phase with a stopped line

Initialize the diameter value as stated above.

Enable the tension control and give the start command to the drive.

If the speed reference calculation is carried out inside the drive (Speed demand en = Enable) the initial

phase is started with the reference set to W offset and with a ramp time Offset acc time.

Now the line can be started.