GEI-100332Ga

——— FUNCTION DESCRIPTION ———

6

58

[386]

Activity

[387]

Ok relay open

Enable seq err

[728]

Activity

[729]

Latch

[730]

Ok relay open

The converters of the DV-300series contain extensive monitoring functions. The effect of possible alarms on the

behaviour of the drive are defined in the PROG ALARMS submenu:
- Saving of alarm status

- How the drive is to react to the alarm

- Indication via the relay between terminal 35 and 36 (central alarm). The switch conditions for the relay can

be defined with the Ok relay func parameter in the CONFIGURATION menu.

- Automatic restart

- Failure reset
For some alarms, the behaviour of the drive can be configured separately. All alarms can also be assigned to a

freely programmable digital output.

Alarm

N.

Factory

Standard

Activity

Latch

Open

OK relay

Hold off

time [ms]

Restart

time [ms]

Failure Supply

Disable drive

ON

ON

-

-

-

Undervoltage

Disable drive

ON

ON

0

1000

Dig. Outp. 7*

Overvoltage

Ignore

ON

ON

0

0

Dig. Outp. 6*

Overspeed

Ignore

ON

ON

0

0

Heatsink

Disable drive

-

ON

-

-

*

Overtemp motor

Disable drive

-

ON

-

-

*

External fault

Disable drive

ON

ON

0

0

*

Brake fault

Disable drive

-

ON

-

-

-

Motor I2t ovrld

Disable drive

ON

ON

-

-

-

Drive I2t ovrld

Disable drive

ON

not programmable

ON

-

-

-

Overcurrent

Ignore

ON

ON

0

0

Dig. Outp. 8*

Field loss

Disable drive

ON

ON

0

0

*

Delta frequency

Ignore

ON

ON

0

0

Speed fbk loss

Disable drive

-

ON

8

-

*

Opt 2 failure

Disable drive

ON

ON

-

-

*

Bus loss

Disable drive

ON

ON

0

0

*

Hw Opt 1 failure

Disable drive

-

ON

-

-

*

Enable seq err

Disable drive

ON

ON

-

-

GD6160g

* This function can be assigned to one of the programmable digital outputs.

If the serial interface or a bus system is used, the alarms can be evaluated via the Malfunction Code parameter.

The parameters required to configure the alarm are shown in Table in Section 10 of the manual.

Activity

Warning

The alarm does not cause reaction of the drive. A warning mes-

sage can be output via a digital output. When the drive is dis-

abled, it will not restart until the failure has been canceled.

Disable drive

The alarm causes the immediate disabling of the converter. The

motor runs to an uncontrolled stop.

Quick stop

When the alarm occurs, the drive stops according to the ramp set in

the RAMP / QUICK STOP menu. The converter is then disabled.

Normal stop

When the alarm occurs, the drive stops according to the ramp

set. The converter is then disabled.

Curr lim stop

When the alarm occurs, the converter brakes with the maximum