DV-300 Adjustable Speed Drives

——— FUNCTION DESCRIPTION ———

6

59

possible current. The converter is then disabled when stopped.

Ignore

No reaction is present. A warning message can be output via a

digital output.

Not all alarms can initiate a controlled stop of the drive. The possibility of setting the

particular “Activity” for individual alarms is described in the table below.

Latch

ON

The alarm is stored. The programmed actions (e.g. opening

the OK relay) are enabled. This status is kept latched even if

the fault condition is restored. A Reset command is required

before a restart.

OFF

In case of alarm, the drive is disabled and the programmed

functions are enabled. The alarm is not latched. When the

failure is removed, the alarm is automatically reset and the

device tries restarting.

Ok relay open

ON

An alarm causes the opening of the potential isolated contact

between terminals 35 and 36.

OFF

The alarm does not cause the opening of the potential free

contact of the OK reay.

Alarm

Ignore

Warning

Disable drive

Quick stop

Normal stop

Curr lim stop

Failure Supply

-

-

X

-

-

-

Undervoltage

-

-

X

-

-

-

Overvoltage

X

X

X

-

-

-

Overspeed

X

X

X

X

X

X

Heatsink

-

X

X

X

X

X

Overtemp motor

X

X

X

X

X

X

External fault

-

X

X

X

X

X

Brake fault

X

X

X

X

X

X

Motor I2t ovrld

X

X

X

-

-

-

Drive I2t ovrld

-

-

X

-

-

-

Overcurrent

X

X

X

-

-

-

Field loss

X

X

X

-

-

-

Delta frequency

X

X

X

-

-

-

Speed fbk loss

-

X

X

-

-

-

Opt 2 failure

-

-

X

X

X

X

Bus loss

X

X

X

X

X

X

Hw Opt 1 failure

-

X

X

X

X

X

Enable seq err

X

-

X

-

-

-

GD6165g

Hold off time

Delay time between the alarm condition detection and the alarm activation. If an alarm

condition occurs the alarm stay OFF for the Hold off time. When this time is elapsed

and the alarm is still present, the alarm activates.

Restart time

If Latch=Off and the alarm condition persists even after the time defined via Restart

time, the alarm is stored and no restart is possible (Latch=OFF).

n

ote

!

In Terminal mode to reset the fault the terminals enable and start must be at zero voltage. The

occurrence of a failure is indicated in the display of the keypad. If “Latch”=ON is selected, a

Reset command is necessary. This can be carried out, for example, by pressing the CANCEL

key on the keypad. If a second error occurs before the first one was reset, the text “Multiple

failures” will appear in the display. In this case, a reset is only possible via Failure reset

parameter in the SPEC FUNCTIONS menu. The reset can be obtained by pressing the ENT

key with a disabled inverter.

Failure supply

Failure on the supply voltage.

It indicates a failure on the internal voltage of the regulation circuit. The message “Failure

supply” occurs if an enabled converter has no voltage on the U2 and V2 terminals. If

it is of a short duration and restored, a possible digital output prepared for the message

is set to a Low condition. A normal reset can be carried out.