GE Industrial Solutions DV-300 DC Drive Users Manual User Manual

Page 69

Advertising
background image

DV-300 Adjustable Speed Drives

——— WIRING PROCEDURES ———

4

25

Code Pieces

European

Europe

American

American

A

3

6KDV3420

S2UF1/110/400A/660V

6KDV3336

A70P400

3

Nr. 20 459 20.400

FWP400

B*

2

S2UF1/110/500A/660V

A70P500

2

Nr. 20 459 20.500

FWP500

D

2

Z14gR32 (GRD2/30)

A70P30

2

Nr. 10 005 07.30

FWP30

A

3

6KDV3500

S2UF1/110/500A/660V

6KDV3400

A70P500

3

Nr. 20 459 20.500

FWP500

B*

2

S2UF1/110/630A/660V

A70P600

2

Nr. 20 459 20.630

FWP600

D

2

Z14gR32 (GRD2/30)

A70P30

2

Nr. 10 005 07.30

FWP30

A

3

6KDV3650

S2UF1/110/630A/660V

6KDV3450

A70P600

3

Nr. 20 4595 20.630

FWP600

B*

2

S3UF1/110/710A/660V

A70P700

2

Nr. 20 460 20.710

FWP700

D

2

Z14gR32 (GRD2/30)

A70P30

2

Nr. 10 005 07.30

FWP30

C**

3

6KDV3770Q2

170M5464/800A/660V

6KDV3560Q2

170M5464/800A/660V

A2-66C800TS

A2-66C800TS

D

2

Z14gR32 (GRD2/30)

A70P30

2

Nr. 10 005 07.30

FWP30

C**

6

6KDV3770Q4

170M5462/630A/660V

6KDV3560Q4

170M5462/630A/660V

A2-66C630TS

A2-66C630TS

D

2

Z14gR32 (GRD2/30)

A70P30

2

Nr. 10 005 07.30

FWP30

C**

3

6KDV310H

170M5464/1000A/660V

6KDV3800

70M5464/1000A/660V

A2-66C1000TS

A2-66C1000TS

D

2

Z14gR32 (GRD2/30)

A70P30

2

Nr. 10 005 07.30

FWP30

C**

6

6KDV310H

170M5464/800A/660V

6KDV3850

170M5464/800A/660V

A2-66C800TS

A2-66C800TS

D

2

Z14gR32 (GRD2/30)

A70P30

2

Nr. 10 005 07.30

FWP30

GD0290g

*

Necessary only for the four quadrant functioning

** These fuses are internally mounted and are provided on the delivery

A

External fuses for the armature converter on the AC input side

B

External fuses for the armature circuit on the direct current side

C

Internal armature fuses for the device starting from type 560A / 770A (American/European)

D

External fuses for the field circuit on the AC input side.

Note: These fuses are necessary only for 6KDV3...Q2A/Q4E Internal fuses are provided for 6KDV3...Q2B/Q4F.

n

ote

!

When with the same letter different fuses are stated, it means that they can be used alternati-

vely. The different types differ for the building forms and for the production house. See the

following indications.

Fuses producer:

Type Z14gR..., GRD2... (E27), Z22gR..., GRD3... (E33)

S... (screw fuses with a distance 80 or 110 mm)

Jean Müller, Eltville

A70P, A2-66C

Gould Shawmut

FWP..., 170 M

Bussmann

n

ote

!

The fuse technical data (dimensions, weights, dissipated powers, fuses carrier etc.), can be

derived from the relative data sheets.

Advertising