DV-300 Adjustable Speed Drives

——— FUNCTION DESCRIPTION ———

6

101

100% (Overload current

2

x Overload time)

• If Motor I2t ovrld is set to Activity = Warning,

the current is maintained at Overload current parameter value

also when Motor I2t accum = 100% (Overload current

2

x

Overload time)

n

ote

!

Motor I2t accum is equal to 100% if (Overload current

2

x Overload time) is reached but

in any case the limit maximum is [(150% FLC)2 x 60 sec]

I2t Drive

The current is limited to T current lim (+/-) value until

Drive I2t accum = 100% i.e. equal to [(150% Derated Drive

Current

(*)

)

2

x 60 sec]. When this value is reached, the drive is

disabled.

I2t Motor & Drv

The current is limited to T current lim (+/-) value until reaching

Drive I2t accum = 100% [(150% Derated Drive Current

(*)

)

2

x

60 sec] if Motor I2t ovrld Activity is set to Warning & Ignore

or, If set to Disable drive until reaching Motor I2t accum =

100% (Overload current

2

x Overload time).

(*)

Derated Drive Current:

If using the drive with Standard sizes (Size selection = Standard) the Derated Drive Current is

calculated as follows:

• Derated Drive Current = Drive size x Derating_fact (see table below)

If using the drive with American sizes (Size selection = American) the Derated Drive Current is

calculated as follows:

• Derated Drive Current = Drive size.

The motor overload function is designed to allow the current selected with Overload

Current for a time equal to Overload Time.

(I load² - I ovld²)*ts[sec] = ((Over Curr / 100)² - 1²)*I Flc² * (Overload time)

I flc = full load current

The motor overload function gives the possibility to have 1.5 the Overload current for 60 sec.

If the threshold is higher than the value is limited to:

(I load² - I Flc²)*ts[sec] = (1.5² - 1²)*I Flc² * 60

The Motor ovrld preal. is available on digital output (code 65), it is 1 with Motor I2t

accum = 90 % and 0 when Motor I2t accum = 0.

The Overld available signal is available on digital output (code 6), it is 0 with Motor

I2t accum = 100 % and 1 with Motor I2t accum 0.

The Drive ovrld preal. is available on digital output (code 66), it is 1 with Drive I2t

accum = 90 % and 0 when Drive I2t accum = 0.

The Overld available signal is available on digital output (code 67), it is 0 with Drive

I2t accum = 100 % and 1 with Drive I2t accum 0.