GEI-100332Ga

——— FUNCTION DESCRIPTION ———

6

6

6.1.3 Fast stop

Parameter description

No.

Value

Standard

Configuration

min

max

Factory

American

Factory

European

Fast/Stop

Fast Stop

No Fast Stop

316

0

1

No Fast Stop No Fast Stop

Terminal 14

+15 ... 30 V

0 V

Terminal 14:

+15 ... 30V = No Fast stop

0V = Fast stop

n

ote

!

The function cannot be actuated via the keypad!

Application: Fast stop is actuated in emergencies and hazardous situations, in order to stop the drive in the

shortest possible time. This method of stopping has the advantage over disconnection in that with a four quad-

rant drive (6KDV3 ... Q4) energy can be recovered in the AC input and the motor can be brought to a halt in a

shorter time than when it coastes down.

The Fast stop command is always required for operation of the converter. A removal of the command when the

drive is running initiates braking with the ramp specified by the parameters Qstp delta speed and Qstp delta

time.

When the drive is brought to a halt, it is still enabled and has torque. The Start command or Enable drive com-

mand must be removed for it to be disconnected.

The drive behavior after the Fast stop command has been given depends on the type of operating mode se-

lected:

- Operation via the terminal strip (Main commands = Terminals):

The drive executes braking until there is no voltage on terminal 14. When voltage is restored, the drive

automatically accelerates to the required reference value (precondition: the other enable commands are still

active).

- Operation via serial line with commands given via terminals too (Main commands = Digital):

The drive executes braking until it has come to a halt. When voltage is restored on terminal 14, there is no

automatic start. This requires the entry of the Start command.

- If the Fast stop command is actuated via the serial interface while there is a voltage present on terminal 14,

the fast stop is executed until the drive is at a halt. The Start command must be entered for the drive to be

restarted.