GE Industrial Solutions DV-300 DC Drive Users Manual User Manual

Page 53

Advertising
background image

DV-300 Adjustable Speed Drives

——— WIRING PROCEDURES ———

4

9

3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

1 2

23 24 25 26 27 28 29 30 31 32 33 34 37 38 39 40 41 42

21 22

Figure 4.4.2: Disposition of terminals from 1 to 42

Table 4.4.6 - A: Terminal Assignment (terminals from 1 to 20)

Terminal

Designation

Function

I/O

Max

voltage

Max

current

1 +2

Configurable analog differntial input

I

±10V

0.25mA

Analog input 1

Signal: Term. 1, Reference point Term. 2

(20mA at current

Factory set for Ramp ref 1*

ref. value)

3 +4

Configurable analog differntial input

I

±10V

0.25mA

Analog input 2

Signal: Term. 3, Reference point Term. 4

(20mA at current

Not factory set

ref. value)

5 +6

Configurable analog differntial input

I

±10V

0.25mA

Analog input 3

Signal: Term. 5, Reference point Term. 6

(20mA at current

Not factory set

ref. value)

7

Reference voltage +10V

O

+10V

10mA

+10V

Reference point: Term. 9

8

Reference voltage -10V

O

-10V

10mA

-10V

Reference point: Term. 9

9

Reference point for the reference voltages on

0V 10

terminal 7 and 8

10

Screen connection (PE) (connected with housing)

11

internal 0V

12

Converter enable

I

+30V

15V/3.2mA

Enable drive

0V

Disabled converter

24V/5mA

+15...30V

Enabled converter

30V/6.4mA

13

Start command

I

+30V

15V/3.2mA

Start

0V

No start command

24V/5mA

+15...30V

Start

30V/6.4mA

14

Fast stop

I

+30V

15V/3.2mA

Fast stop

0V

Fast stop

24V/5mA

+15...30V

No Fast stop

30V/6.4mA

15

External fault

I

+30V

15V/3.2mA

External fault

0V

External fault present

24V/5mA

+15...30V

No external fault present

30V/6.4mA

16

Reference point of the digital inputs,

COM ID

terminals 12 to 15

18

Reference point of the 24V voltage

0V 24

on terminal 19

19

Voltage +24V

O

+20...30V

200 mA**

+24 V

Reference point Terminal 18

20

Screen connection (PE) (connected w/housing)

GD0180g

*

The user can adapt the configuration to the requirements of the application concerned via the keypad, the serial interface or a
bus connection.

** Total value including Terminal 19, Pin 2 of connector XE2 and the digital outputs on the option card 6KCV300TBO.

Advertising