6 ramp, Figure 6.6.1 : ramp circuit – GE Industrial Solutions DV-300 DC Drive Users Manual User Manual

Page 154

Advertising
background image

GEI-100332Ga

——— FUNCTION DESCRIPTION ———

6

26

6.6 RAMp

Quick stop

F

Ramp Reference

F

Linear

S-shape

T

Freeze ramp

COMMAND

From

Ramp in = 0

To Speed Reference

generation

Multi Ramp Function

Speed

t

S-shape

T

0

t

Linear

Acc. delta speed

100 rpm

Dec. delta speed

100 rpm

Acc. delta time

1 s

Dec delta time

1 s

QStp delta speed

1000 rpm

Enab multi rmp

QStp delta time

1 s

Ramp +/- delay

100 ms

Ramp ref (d)

Ramp shape

S shape t const

300 ms

S acc t const

300 ms

S dec t const

300 ms

Ramp +

Ramp -

Freeze ramp

Ramp shape

Figure 6.6.1 : Ramp circuit

The ramp (reference value integrator) determines the acceleration and deceleration times of the drive. These

times can be set independently of each other.
An additional ramp is provided for a quick stop. This ramp can only be activated via the serial interface or a field

bus.
The ramp can either be linear or S-shaped..
The reference values can be defined in different ways

- with the Ramp ref 1 and/or Ramp ref 2 reference values

- with the multi-speed function

- with the motor potentiometer function

- with the Jog function

The Ramp generator can be used in a stand alone configuration. When the Ramp generator is disabled (Enable

ramp = disabled), the Enable drive, Start/Stop and Fast stop commands have no more influence on Ramp

generator. In such a condition it is free to run and can be used separately.