Figure 6.12.3.1: digital outputs, Refer to paragraph 6.16.3 pid function, Brake alarm signal – GE Industrial Solutions DV-300 DC Drive Users Manual User Manual

Page 202: I2t motor overload alarm signal

Advertising
background image

GEI-100332Ga

——— FUNCTION DESCRIPTION ———

6

74

Drive Relay Output

D02

D06

27

7

COM_DO

COM_DO

25

5

D03

D07

28

8

COM_DO

COM_DO

25

5

D04

D08

29

9

COM_DO

COM_DO

25

5

R2NO

75

R2COM

76

D01

D05

26

6

COM_DO

COM_DO

25

5

R1NO

35

R1COM

36

TBO integrated (pos.” A”)

TBO card pos. B (option)

Ok relay func.

Drive healthy

Relay 2

Stop control

Digital output 1

Digital output 5

Ramp +

Curr limit state

Inversion out 2

Inversion out 6

Inversion out 3

Inversion out 7

Inversion out 4

Inversion relay 2

Inversion out 8

Inversion out 1

Inversion out 5

Digital output 2

Digital output 6

Ramp -

Overvoltage

Digital output 3

Digital output 7

Spd threshold

Undervoltage

Digital output 4

Digital output 8

Overld available

Overcurrent

Figure 6.12.3.1: Digital outputs

Digital output XX

Selection of the parameter that is assigned to the digital output concerned. The following

assignments are possible:

OFF

Speed zero thr

Spd threshold

Set speed

Curr limit state

Drive ready

Mot ovrld avail

6)

Overload state

Ramp +

Ramp -

Speed limited

Undervoltage

Overvoltage

Heatsink

Overcurrent

Overtemp motor

External fault

Failure supply

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

Pad A bit

Pad B bit

Virt dig input

Torque sign

Stop control

Field loss

Speed fbk loss

Bus loss

Hw opt1 failure

Opt2 failure

Encoder 1 state

Encoder 2 state

Enable seq err

Diameter calc st

1)

Drive healthy

13)

Input 1 cp match

Diam reached

Spd match compl

18

19

20

21

23

24

25

26

28

29

30

31

35

38

42

49

58

59

Acc state

Dec state

Brake comand

2)

Brake failure

3)

Mot ovrld preal

4)

Dvr ovrld preal

5)

Dvr ovrld avail

7)

I2t mot ovrld fail

8)

I2t drv ovrld fail

9)

Mot cur threshld

10)

Overspeed

11)

Delta frequency

12)

Drv rdy to start

14)

BUS control mode

15)

60

61

62

63

65

66

67

68

69

70

71

72

76

77

1)

Refer to paragraph 6.16.3 PID function

2)

brake relay control; indicates the presence of adequate current to support the load

(Torque proving) parameter..

3)

brake alarm signal.

4)

this signal is enabled when the thermal image of the motor Motor I2t accum =

90 % and returns to 0 when Motor I2t accum = 0.

5)

this signal is enabled when the thermal image of the drive Drive I2t accum = 90

% and returns to 0 when Drive I2t accum = 0.

6)

The default condition of this signal is enabled. It is disabled when Motor I2t accum

= 100 % and is re-enabled when Motor I2t accum = 0.

7)

The default condition of this signal is enabled. It is disabled when Drive I2t accum

= 100 % and is re-enabled when Drive I2t accum = 0.

8)

I2t motor overload alarm signal.