DV-300 Adjustable Speed Drives

——— FUNCTION DESCRIPTION ———

6

25

Example of the function of the Current lim red and Torque reduct parameters.

T current limit (or T current lim +/-) = 80 %

Current lim red = 70 %

Torque reduct = High (not active)

Current limit = 80 %

Torque reduct = Low (active)

Current limit = 70 %

The value for T current limit can be set in the START UP\Limits menu.

6.5.3 Flux limits

LIMITS

Flux limits

[467]

Flux current max [%]

[468]

Flux current min [%]

Parameter description

No.

Value

Standard

Configuration

min

max

Factory

American

Factory

European

Flux current max [%]

467

P468

100

100

100

*/**

Flux current min [%]

468

0

P467

5

5

-

* This parameter can be set on a programmable analogic outputs.

** This parameter can be set on a programmable analogic input.

The limits regarding the field current are set in this submenu.

Flux current max

Percentage of maximum field current according to the Motor nom flux parameter.

The max. value (100%) corresponds to the circulation in the field circuit of the motor ,

of a current equal to the value set in Motor nom flux.

If any curve has been set via I field cnst parameter, the variation of this parameter influ-

ences the field current in a linear way .

(see Flux /if curve section 5.4.5)

Flux current min

Percentage of minimum field current according to the Motor nom flux parameter .

Its value states the circulation in the field circuit of the motor , of a minimum current

compared to the value set in Motor nom flux.

The value set here affect the threshold of the “Field loss” alarm indication. The

threshold is the half of Flux current min.