4 control section – GE Industrial Solutions DV-300 DC Drive Users Manual User Manual

Page 33

Advertising
background image

DV-300 Adjustable Speed Drives

——— DESCRIPTION, COMPONENT IDENTIFICATION AND SPECIFICATIONS ———

2

13

2.4.4 Control section

Enables

0 / 15...30 V

3.2...6.4 mA (approx. 5 mA at 24 V)

Analog inputs

option

0... ± 10 V

0.25mAmax

0...20 mA

10 V max

4...20 mA

10 V max

Analog outputs

0...± 10 V

5 mA max each output

Digital inputs

0 / 15...30 V

3.2...6.4 mA (approx. 5 mA at 24 V)

Digital outputs

supply

+ 15...35 V

signal

+ 15...35 V

20 mA max each output

Encoder inputs

Sinusoidal

voltage

1 V pp

current

8.3 mA pp each channel (input resistance = 124 ohm)

pulses per rev

min 600

max 9999

max frequency

150 kHz

max cable lenght

screened, 150m (0.75 mm

2

) / 125m (0.5 mm

2

) / 55m (0.22 mm

2

)

Digital

voltage

5V TTL / 15...24V HTL (H logic)

current

4.5 mA / 6.8 ... 10.9 mA each channel with H logic

pulses per rev

min 600

max 9999

max frequency

150 kHz

max cable lenght

screened, 150m (0.75 mm

2

) / 125m (0.5 mm

2

) / 55m (0.22 mm

2

)

Analog tachogenerator input

voltage

22.7 / 45.4 / 90.7 / 181.6 / 302.9 V max,

depending on the switch S4 setting

current

8 mA full scale

max cable lenght

screened, the max length depends on the installation, typical 150m

Internal supply voltage

max load

+ 5 V

160 mA

encoder connector, PIN 7/9

(only for sinusoidal encoder)

+ 10 V

10 mA

terminal 7

- 10 V

10 mA

terminal 8

+ 24 V

200 mA

terminal 19

encoder connector, PIN 2/9

(only for digital encoder)

tolerance

+ 10 V

± 3 %

1)

- 10 V

± 3 %

1)

+ 24 V

+ 20 ... 30 V, not stabilized

1)

The values of the voltages + 10V and -10V are the same. The stated tolerance refers to the voltage width.

Advertising