GE Industrial Solutions DV-300 DC Drive Users Manual User Manual

Page 49

Advertising
background image

DV-300 Adjustable Speed Drives

——— WIRING PROCEDURES ———

4

5

Table 4.3.5: Cable size for power field terminals U1, V1, C1, D1

American

European

max cable section

[mm2]

AWG

Tightening torque

[Nm]

6KDV3017...

6KDV3020...

0.2...4

24...10

0.5...0.8

6KDV3035...

6KDV3040...

6KDV3056...

6KDV3070...

6KDV3088...

6KDV3110...

6KDV3112...

6KDV3140...

6KDV3148...

6KDV3185...

6KDV3224...

6KDV3280...

6KDV3280...

6KDV3350...

6KDV3336...

6KDV3420...

6KDV3400...

6KDV3500...

6KDV3450...

6KDV3650...

6KDV3560...

6KDV3770...

6KDV3800...

6KDV310H

6KDV3850

GD0130g

The following sizes are provided with terminal blocks:

U/V/W/C/D:

AWG 5 - 3/0 (16-95 mm

2

), stranded Cu

PE:

AWG 5 - 1 (16-50 mm

2

), stranded Cu

The following AWG and torque are required for field wiring:

Device

AWG

Tightening torque [Nm]

6KDV3088…

2

12

6KDV3112…

1/0

12

6KDV3148…

3/0

12

earth

-

12

GD0136g-a

n

ote

!

When connecting the converter, a 9.5 mm (3/8 in.) spacing between uninsulated live parts of

opposite polarity should be mantained.

n

ote

!

The DV-300 converters are UL listed only when used with the above mentioned terminal kits.

Table 4.3.6: Cable size for fans, signals, thermistors and regulation supply

Terminals

Max connection cable section

Tightening torque

[Nm]

flexible [mm

2

]

multi-core [mm

2

]

AWG

PE

2.5...10

2.5...10

12...8

2

U2, U3, V2, V3, 35, 36, 75, 76, 78, 79

0.14...1.5

0.14...2.5

26...14

0.5

T0140g