DV-300 Adjustable Speed Drives

——— FUNCTION DESCRIPTION ———

6

89

If the Motor pot up and Motor pot down commands are given at the same time, they will not change the speed

reference value. The last speed reference value is saved when the drive is switched off or if there is a fault. When

the drive is restarted, it accelerates to this speed according to the ramp set. If the command Motor pot reset is

given with the drive switched off, the speed reference value is deleted and the drive starts at zero speed. If the

status of theMotor pot sign command is changed while the drive is running, the drive will reverse according

to the specified ramp times.
When using the motor potentiometer function, the ramp must be enabled and the Start command must be present.

6.14.2 Jog function

FUNCTIONS

Jog function

[244]

Enable jog

[265]

Jog operation

[375]

Jog selection

[266]

Jog reference [FF]

Parameter description

No.

Value

Standard

Configuration

min

max

Factory

American

Factory

European

Enable jog

Enabled (1) / Disabled (0)

244

0

1

Disabled

Disabled

-

Jog operation

265

-

-

-

-

Jog selection

Speed input (0) / Ramp input (1)

375

0

1

0

0

-

Jog reference [FF]

266

0

32767

0

0

**

Jog +

No jog forwards (0)

Forwards jog (1)

398

0

1

*

Jog -

No backwards jog (0)

Backwards jog (1)

399

0

1

*

* This function can be assigned to one of the programmable digital inputs.

** This parameter can be assigned to a programmable analog input.

Enable jog

Enabled

Enabled Jog function (this selection is possible only when the

drive is switched off).

Disabled

Disabled Jog function

Jog operation

Pressing the “+” and “-” keys on the keypad enables the drive to be moved forward and

backward. In connection with the 6KDV3 ... Q4 converters it is possible to operate the

Jog function in an anti-clockwise rotation by pressing the “-” key.

+

Jog clockwise rotation

-

Jog counter-clockwise rotation

Jog reference

Reference value for jog mode. Defined by the units, specified by the factor function.

Jog selection

This parameter determines if the Jog function reference must go through the ramp or

directly to the speed regulator.

Speed input

The Jog reference is directly defined. The ramp is not active.

Ramp input

The Jog reference is defined with a set ramp.

Jog +

High

Clockwise Jog function when the Jog function is enabled and

the Start command is not present.

Low

Disabled

Jog -

High

Counter-clockwise Jog function for the 6KDV3 ... Q4 when the

Jog function is enabled and the Start command is not present.