Table 4.6.1.1: terminal strip connections – GE Industrial Solutions DV-300 DC Drive Users Manual User Manual

Page 58

Advertising
background image

GEI-100332Ga

——— WIRING PROCEDURES ———

4

14

4.6.1 Assignment of the plug-in terminal strip (terminals 1...15) for Option Card 6KCV300TBO

Table 4.6.1.1: Terminal strip connections

Designation

Function

I/O

Max

voltage

Max

current

1

Analog output 1

(3)

Analog output 1 (3)

Reference point: Terminal 2

Factory set for T current (motor current)

O

±10V

5mA

2

COM analog

output 1

Reference point of analog output 1 (Terminal 1)

3

Analog output 2

(4)

Analog output 2 (4)

Reference point: Terminal 4

Factory set for motor speed ( Current U)

O

±10V

5mA

4

COM analog

output 2

Reference of analog output 2 (Terminal 3)

5

COM digital

outputs

COM digital outputs (Terminals 6...9)

6

Digital output

1 (5)

Digital output 1 (5)

COM: Terminal 5

Factory set for Ramp + (Curr limit state)

O

+30V

50mA

7

Digital output

2 (6)

Digital output 2 (6)

COM: Terminal 5

Factory set for Ramp - (Overvoltage)

O

+30V

50mA

8

Digital output

3 (7)

Digital output 3 (7)

COM: Terminal 5

Factory set for Spd threshold (Undervoltage)

O

+30V

50mA

9

Digital output

4 (8)

Digital output 4 (8)

COM: Terminal 5

Factory set for Overload available (Overcurrent)

O

+30V

50mA

10

Supply digital

outputs

Supply voltage for digital outputs

I

+30V

depends on

the load

max 80mA

11

Digital input

1 (5)

Digital input 1 (5)

COM: Terminal 15

Not Factory set

I

+30V

15V/3.2mA

24V/5mA

30V/6.4mA

12

Digital input

2 (6)

Digital input 2 (6)

COM: Terminal 15

Not Factory set

I

+30V

15V/3.2mA

24V/5mA

30V/6.4mA

13

Digital input

3 (7)

Digital input 3 (7)

COM: Terminal 15

Not Factory set

I

+30V

15V/3.2mA

24V/5mA

30V/6.4mA

14

Digital input

4 (8)

Digital input 4 (8)

COM: Terminal 15

Not Factory set

I

+30V

15V/3.2mA

24V/5mA

30V/6.4mA

15

COM digital

inputs

COM of the digital inputs (Terminals 11...14)

GD0240g