2 speed ref – GE Industrial Solutions DV-300 DC Drive Users Manual User Manual

Page 146

Advertising
background image

GEI-100332Ga

——— FUNCTION DESCRIPTION ———

6

18

Parameter description

No.

Value

Standard

Configuration

min

max

Factory

American

Factory

European

Ramp ref 1 [FF]

Ramp ref 1 (%)

44

47

-2 P45

-200.0

+2 P45

+200.0

0

0.0

0

0.0

An. Input 1

(Terminals 1 + 2)*

Ramp ref 2 [FF]

Ramp ref 2 (%)

48

49

-2 P45

-200.0

+2 P45

+200.0

0

0.0

0

0.0

*

Ramp ref (rpm)

Ramp ref (d) [FF]

Ramp ref (%)

110

109

111

-32768

-32768

-32768

+32767

+32767

-200.0

-

-

+200.0

-

-

-

**

* This function can be assigned to one of the programmable analog inputs. The converter is already

fatory set for a configuration using the terminals stated. The setting can also be modified to suit the

application at hand.

** This parameter can be assigned to a programmable analog output.

Ramp ref 1

1st reference value for the ramp. The value to be entered depends on the factor function.

Ramp ref 1 (%)

1st reference value as a percentage of the Speed base value

Ramp ref 2

2nd reference value for the ramp. The value to be entered depends on the factor function.

Ramp ref 2 (%)

2nd reference value as a percentage of the Speed base value

Ramp ref (rpm)

Total reference value for the ramp in rpm (revolutions per minute)

Ramp ref (d)

Total reference value for the ramp in the dimension specified by the factor function.

Ramp ref (%)

Total reference value of the ramp as a percentage of the Speed base value

n

ota

:

Speed base value cannot exceed 8192 rpm

The total Ramp reference value Ramp ref consists of the signed addition of Ramp ref 1 and Ramp ref 2 (see

Figure 6.4.1.1).
Example 1:

Ramp ref 1 = + 50 % Ramp ref 2 = + 30 %

Ramp ref = 50 % + 30 % = 80 %

Example 2:

Ramp ref 1 = + 40 % Ramp ref 2 = - 60 %

Ramp ref = 40 % - 60 %= - 20 %

0 ... 10 V, 0 ... 20 mA and 4 ... 20 mA signals can be used when setting the reference value via terminals.
The Ramp ref (rpm), Ramp ref (d) and Ramp ref (%) are influenced by the minimum speed limits. These are

directly applied on the Ramp ref 1, as well as the Motor potentiometer and Multispeed references.

6.4.2 Speed ref

INPUT VARIABLES

Speed ref

Speed ref 1

[42]

Speed ref 1 [FF]

[378]

Speed ref 1 (%)

Speed ref 2

[43]

Speed ref 2 [FF]

[379]

Speed Ref 2 (%)

The speed reference value specifies the required speed of the drive. The drive responds to the reference value

progression directly, except in cases where the torque available is insufficient for this purpose. In this case, the

drive operates at current limit until the selected speed has been reached. The speed reference value determines

the speed of the motor, while the polarity determines the directíon of rotation.