——— FUNCTION DESCRIPTION ———

6

32

6.7.1 Speed regulator

SPEED REGULAT

[118]

Speed ref [rpm]

[236]

Speed reg output [% ]

[322]

Lock speed reg

[242]

Enable spd reg

[348]

Lock speed I

[1016]

Aux spd fun sel

[444]

Prop filter [ms]

Parameter description

No.

Value

Standard

Configuration

min

max

Factory

American

Factory

European

Speed ref [rpm]

118

-32768

+32767

-

-

**

Speed reg output [% ]

236

-200

+200

see 6.7.1

-

-

T current ref 1 **

Lock speed reg

ON (1)

OFF (0)

322

0

1

OFF

OFF

*

Enable spd reg

Enable (1)

Disable (0)

242

0

1

Enabled

Enabled

-

Lock speed I

Active (0)

Not active (1)

348

0

1

Not active (1) Not active (1)

*

Aux spd fun sel

Speed up (0)

Inertia-loss cp (1)

1016

0

1

Speed up (0) Speed up (0)

Prop filter [ms]

444

0

1000

0

0

* This function can be assigned to one of the programmable digital inputs.

** This parameter can be assigned to a programmable analog output.

Speed ref

Total speed reference value in rpm

Speed reg output

Output value of the speed regulator, used as the reference value for the current regulator

n

ote

!

The speed regulator is still active even if disabled (Enable spd reg = Disabled),

therefore the Speed reg output contains valid information also in this case.

Such a data can be transferred to the 6KCV300DGF board to be used for other

regulation. If the speed regulator is enabled (Enable spd reg = Enabled) the

Speed reg output contains the sum of the actual speed regulator output and

T current ref 2.

Lock speed reg

This parameter is used in order to lock the speed regulator. When this happens, it stops to

work, the current reference value is set to zero and the drive comes to a stop. This coast-

ing time then depends on the rotating mass and the friction within the system concerned.

If the connection between the speed regulator and the current regulator is restored, the

drive will restart in the shortest possible time.

ON

Speed regulator locked (= 0 V when using a digital input).

OFF Speed regulator unlocked (= 15...30 V when using a digital input).

Enable spd reg

This parameter can only be changed when the drive is switched off.

Enabled

The speed regulator is enabled. The regulator output is connected

to the input of the current regulator. Speed reg output = T cur-

rent ref 1

Disabled

The speed regulator is disabled.