DV-300 Adjustable Speed Drives

——— FUNCTION DESCRIPTION ———

6

53

Index storing parameter [13]

No. bit

Name

Description

Access

(Read/Write)

Default

0

Source Enc

Num

It indicates to which encoder the values in this register are referred to:

0 = register data are referred to the Encoder 1

1 = register data are referred to the Encoder 2

R

0

1

MP_IN

Actual Qualifier level value:

0 = qualifier input level is low

1 = qualifier input level is high

R

0

2-3

STATNLT Status of the acquisition function:

0 = Switched off

1 = Once, storing is not executed yet

2 = Once, storing is already executed

3 = Continuous

R

0

16-31

CNTNLT Position counter value corresponding to the index. 0 = Switched off

Value is only valid when STANLT is equal to 2 or 3

R

0

Ay6126B

6.11.5 “Standard / American” selection, Software Version

CONFIGURATION

Drive type

[465]

Drive size [A]

[201]

2B + E

[464]

Size selection

[331]

Software version

Parameter description

No.

Value

Standard

Configuration

min

max

Factory

American

Factory

European

Drive size [A]

465

0

S

S

S

-

2B + E

ON (Off) (0)

OFF (On) (1)

201

0

1

0

0

-

Size selection

Standard (0)

American (1)

464

0

1

1

0

-

Software version

331

-

Drive type

DV-300...Q2

DV-300...Q4

300

10

11

S

S

-

Drive size

Display of the converter armature current in ampere (it is codified by the SW15 Switch

placed on the R-TPD32-GE. regulation card). The stated value depends on the setting

of the Size selection parameter.

2B + E

Selection of the Q2 + external excitation configuration. Only for Q2 converters. The

function allows the drive to work with an external 4 quadrant field controller. When

the parameter is On the Ramp / Speed / T current references and Speed measurement

have the same behaviour of the Q4 drive.

Size selection

With the “Standard” selection the converter produces rated current in a continuative

way in the preset ambient conditions without overload (for overload see 6.14.5). With

“America” selection the rated current is defined considering an overload of 1.5 times for

60 seconds. This causes a reduction of the converter rated current (continuative current)

for the same type of drive. See section 4.4, R-TPD32-GE Regulation card.

Standard

The converter produces rated current in a continuative way. It

is stated as Drive size. No overload functions are set.