GEI-100332Ga

——— CONVERTER OPERATION ———

5

42

Measurement error messages

These messages may occour when extreme parameter values have to be identified. It can be useful to retry the

self tune command when any of the following messages occours. If messages persist, alternative manual tuning

procedures should be used.

Description

Note

“Over speed”
“Drive stalled”:

Increase value of parameter Test T curr lim and repeat Self tuning

“Load applied”:

Nominal zero load torque at standstill was detected. Self tuning is impossible for this

type of load.

“T curr too high”:

Reduce value of Test T curr lim parameter for Self tuning

“Friction null”:

Value of friction is zero or lower than the accuracy limit of the control system

5.3.5.3 Field converter

The default DV-300 converters are set to operate without Voltage control. The following settings must be taken

into consideration when a functioning in Voltage control is needed or when the field of the connected motor is

not power supplied via the converter.
All the settings described in this chapter must be carried out in disable condition (no voltage on terminal 12).

Selection of the functioning system

- With a constant field current:

Flux reg mode = Constant current

Enable flux reg = Enabled

- With Voltage control:

Flux reg mode = Voltage control.

In the CONFIGURATION menu set the max output

voltage via the Max out voltage parameter.

Enable flux reg = Enabled

- Field circuit not supplied by DV-300 Flux reg mode = OFF

Enable flux reg = Disabled

Setting the rated field current

- Set the rated field current of the motor via the Motor nom flux parameter.
- When the field motor current is substantially lower than the rated current of the field converter, adapt trough

the S14 dip switches the field converter. It must be configured according to the table 5.3.5.3.1 Via the Nom

flux curr parameter it is possible to select the new field rated current.

- For fixed field current operation, if the actual motor (base) field current ≤ 10% of the maximum rating of

the field package it is required to calibrate the field current feedback scaling using dipswitch S14.

- For weak field operation, also referred as “CEMF field control” or “crossover field control”, if the top base

speed Motor nom flux ≤ 10% of the maximum rating of the field package it is required to calibrate the

field current feedback scaling using dipswitch S14.

Calibration to the exact field current setting is not required, as long as the above conditions are met.
Calibration is not required if the field control is provided by a separate field converter.