6.17.2 Torque calculation

The torque calculator is made of three blocks:
1.

Torque calculation according to the winder/unwinder ray and to the set tension: C = T x r

2.

Calculation of the static, dynamic and inertial compensations

3.

If the Taper function is enabled, the calculation of the tension curve is made according to the ray.

The tension and Taper reduction references can be sent via an analog input, serial line or field bus. The calculation

of the angular acceleration, necessary to the inertial compensations, can be carried out through asuitable internal

function or by stating via three digital inputs the acceleration, deceleration and fast deceleration conditions.
The connection to the PID function belongs to the compensation block. Such connection is necessary when a

closed loop tension control with loading cell is carried out.
The calculation result is sent directly to the drive current limits and can be monitored in the parameters In use

Tcur lim + and In use Tcur lim – of the LIMITS menu.
The standard parameters T current lim +/- and the limits set by the programmable overload function are anyway

active in order to protect both the inverter and the motor; the setting with the lowest value is always the most

important. It is also possible to set a specific current limit for the coil “launching” function during an automatic

switching. The outcoming tension value and that of the calculated torque current can be monitored on the analog

outputs.

OPTIONS

Torque winder

Torque calculat

[1180]

Tension ref [%]

[1181]

Tension scale [%]

[1194]

Act tension ref [%]

[1193]

Torque current [%]

Parameter description

No.

Value

Standard

Configuration

min

max

Factory

American

Factory

European

Tension ref [%]

1180

0.00

199.99

0

0

*

Tension scale [%]

1181

0

200

100

100

Act tension ref [%]

1194

0.00

199.99

Torque current [%]

1193

0.00

200.00

**

*

This parameter can be set on a programmable analog input.

** This parameter can be set on a programmable analog output.

Tension ref

Per cent tension reference.

Tension scale

Scale factor of the torque current in %.

This parameter is used when the value of the maximum winding torque has to be limited

or when a closed loop control is used in order to adjust the torque current value to the

real tension on the material measured by the loading cell.

As for tuning refer to paragraph Application example.

Act tension ref

Monitor of the % tension reference less the Taper percentage set via Tension red; if the

Taper function is not enabled, it corresponds to Tension ref.

Torque current

Monitor for the requirement of the torque current in %.