Manual tuning of field current regulator – GE Industrial Solutions DV-300 DC Drive Users Manual User Manual

Page 121

Advertising
background image

DV-300 Adjustable Speed Drives

——— CONVERTER OPERATION ———

5

45

20.00 ms/DIV

20.00 ms/DIV

20.00 ms/DIV

20.00 ms/DIV

Manual tuning of field current regulator

n

ote

!

In the majority of the cases the dc motors with an independent excitation operate with a

direct field (Flux reg mode = Constant current). In this case it is not necessary to optimize

the regulator of the field current and the regulator of the armature voltage.

The optimization showed below, refers to drives operating with constant power range (armature and field mixed

regulation). In these cases it is necessary to configurate the field converter for this particular use. See below.

n

ote

!

During the optimization of the regulator of the field current, the converter must not receive

a Start command.

- Converter disabled (no voltage on terminal 12)
- Menu LIMITS / Flux limits: Flux current max = 100% equal to the rated field current of the motor.

Flux current min = 0

- Set at 0.00 the Flux I and Flux P parameters in the REG PARAMETERS / ...menu .
- Measure the field current via an analog output. To this purpose the variable “Flux current” has to be param-

eterized on one output and the variable “Flux reference” on another (see “Input/Output programming”).

- Select the FLUX REGULATION menu.

Figure 5.3.6.1: Above: Actual spd; Below: Motor

current. Speed P too low.

Figure 5.3.6.2: Above: Actual spd; Below: Motor

current. Speed P too high.

Figure 5.3.6.3: Above: Actual spd; Below: Motor

current. Speed I too high.

Figure 5.3.6.4: Above: Actual spd; Below: Motor

current. Speed P and Speed I set correctly.