——— FUNCTION DESCRIPTION ———

6

28

The deceleration of the drive is defined as a quotient of the parameters Dec delta speed and Dec delta time (see Figure

6.6.1.1). As for the four quadrant converters (6KDV3 ... Q4...) it is the same for both directions of rotation.
The Quick Stop function provides the possibility of a second deceleration ramp for the emergency braking of

the drive. The ramp output in this case is not set to zero immediately but after a set time. The deceleration of

the drive via the Quick Stop function is defined as the quotient of the Qstp delta speed and Qstp delta time

parameters. As for the four quadrant converters (6KDV3 ... Q4...) it is the same for both directions of rotation.

This ramp is activated by the functions Fast stop (via terminals) and Quick stop.

6.6.2 Ramp shape and control commands

RAMP

[18]

Ramp shape

[19]

S shape t const [ms]

[663]

S acc t const [ms]

[664]

S dec t const [ms]

[20]

Ramp +/- delay [ms]

[673]

Fwd-Rev

[245]

Enable ramp

[344]

Ramp out = 0

[345]

Ramp in = 0

[373]

Freeze ramp

Parameter description

No.

Value

Standard

Configuration

min

max

Factory

American

Factory

European

Ramp shape

Linear (0)

S-Shaped (1)

18

0

1

Linear (0)

Linear (0)

-

S shape t const [ms]

19

100

3000

300

300

-

S acc t const [ms]

663

100

3000

300

300

-

S dec t const [ms]

664

100

3000

300

300

-

Ramp +/- delay [ms]

20

0

65535

100

100

-

Fwd-Rev

No direction (0)

Fwd direction (1)

Rev direction (2)

No direction (3)

673

0

3

1

1

-

Forward sign

293

0

1

0

0

-

Reverse sign

294

0

1

0

0

-

Enable ramp

Enabled (1)

Disabled (0)

245

0

1

Enabled (1)

Enabled (1)

-

Ramp out = 0

Active (0)

Not active (1)

344

0

1

Not active (1) Not active (1)

*

Ramp in = 0

Active (0)

Not active (1)

345

0

1

Not active (1) Not active (1)

*

Freeze ramp

Active (0)

Not active (1)

373

0

1

Not active (1) Not active (1)

*

Ramp +

Acc.CW + Dec. anti-CW (1)

Other states (0)

346

0

1

-

-

Digital output 1 *

Ramp -

Acc.anti-CW + Dec. CW (1)

Other states (0)

347

0

1

-

-

Digital output 2 *

* This function can be assigned to one of the programmable digital inputs.

** This parameter can be assigned to a programmable digital output.

*** This function can be assigned to one of the programmable analog outputs.