Output voltage, Armature circuit, Field circuit – GE Industrial Solutions DV-300 DC Drive Users Manual User Manual

Page 32: Table 2.4.3.3: armature circuit output votages, Table 2.4.3.4: field circuit output votages, Output voltage armature circuit field circuit

Advertising
background image

GEI-100332Ga

——— DESCRIPTION, COMPONENT IDENTIFICATION AND SPECIFICATIONS ———

2

12

Output voltage

The below mentioned output voltages take into account an AC input undervoltage within the stated tolerance

limits and a voltage drop of 4% due to the inserted AC input reactors. It is the same as the rated armature voltage

suggested for the connected motor.

Armature circuit

Table 2.4.3.3: Armature circuit output votages

AC input voltage

Output Armature voltage (Terminals C / D)

(Terminals U / V / W)

Two quadrant converter

Four quadrant converter

230 V ±10 %, 3Ph

260 V

240 V

400 V ±10 %, 3Ph

470 V *

420 V *

440 V ±10%, 3Ph

530 V

460 V

460 V ±10%, 3Ph

560 V

480 V

480 V ±10%, 3Ph

580 V

500 V

GD0080g

*

Voltage measured as per DIN 40 030 (09/93)

As for 6KDV3...Q2C / Q4G converters see Appendix A (GEI-100332C).

Field circuit

Table 2.4.3.4: Field circuit output votages

AC input voltage

Output field voltage** (Terminals C1/D1)

(Terminals U1 / V1)

Fixed field

Adjustable field

230 V ±15 %, 1Ph

200 V *

200 V *

400 V ±15 %, 1Ph

310 V *

310 V *

460 V ±10%, 1Ph

360 V

360 V

GD0080g

*

Voltage measured as per DIN 40 030 (09/93)

** The max field voltage is equal to 0.85 x AC input line voltage

n

ote

!

The minimum AC input voltage supply value for the field circuit is 110VAC.

As for 6KDV3...Q2C / Q4G converters see Appendix A (GEI-100332C).