GEI-100332Ga

——— CONVERTER OPERATION ———

5

4

Selection from predefined values

ENT

FLUX REGULATION
Flux reg mode

-/+

Flux reg mode

-/+

Field weakening

CANC

ENT

Flux reg mode

-/+

Constant current

Flux reg mode

-/+

OFF

+

+

-

-

ok

Return without changes

CANC

ENT

ok

CANC

ENT

ok

Return without changes

Return without changes

- The parameters that can be selected among the several possiblities are marked with -/+ on the keypad dis-

play.

- To change a value press ENT. The current value is shown in the display. This can be changed with the +

and - keys.

- Confirm the new value and return to the previous display by pressing ENT.
- Return without changes via CANC

Autotuning of Analog input

ENT

Analog input 1

Auto tune inp 1

Auto tune inp 1

Tuning

Auto tune inp 1

Ready

- Select the parameter Auto tune input XX.
- Press ENT
- The tuning procedure will run automatically. The messages “Tuning” and “Ready” will appear in succession

before the original parameter is shown.

n

ote

!

The maximum signal possible must be present on the analog input concerned during the

tuning procedure.