GEI-100332Ga

——— FUNCTION DESCRIPTION ———

6

24

speed

torque

T current lim +

T current lim -

T current lim -

T current lim +

speed

torque

T current lim +

T current lim -

T current lim -

T current lim +

+1% of Motor nom speed

-1% of Motor nom speed

Figure 6.5.2.1 Torque limits with T curr lim type = T lim +/-

Figure 6.5.2.2: Torque limits with T curr lim type = T lim mot/gen

T current lim

Symmetrical current limit for both current directions for 6KDV3 ... Q4 converters.

Defined as a percentage of the Full load curr parameter. The maximum value depends

on the Enable overload parameter.

Enable overload

Disabled

T current limit

100 % max

Enable overload

Enabled

T current limit

200% max

If the T current limit parameter is changed, the Parameter T current lim + and T current

lim - parameters are set to the same value. If both these parameters are subsequently

changed, the last change is valid.

T current lim +

Setting of the drive current limit for the positive current direction (clockwise drive and

counter-clockwise brake). Entered as a percentage of the Full load curr value. The

maximum value depends on the value of the Enable overload parameter.

Enable overload

Disabled

T current lim+

100 % max

Enable overload

Enabled

T current lim+

200% max

T current lim -

Setting of the drive current limit for the negative current direction (counterclockwise

drive and clockwise brake). Entered as a percentage of the Full load curr parameter.

The maximum value depends on the value of the Enable overload parameter. This

parameter is not active for the 6KDV3 ... Q4 converters.

Enable overload

Disabled

T current lim-

100 % max

Enable overload

Enabled

T current lim-

200% max

Curr limit state

Status message, indicating whether the drive is working with the set current limit or not.

High Drive working at the current limit. “I

Limit

” LED lights up.

Low Drive not working at the current limit.

In use Tcur lim +

Status message, indicating the used value of the current limit for the positive torque

direction as a percentage of Full load curr.

In use Tcur lim -

Status message, indicating the used value of the current limit for the negative torque

direction as a percentage of Full load curr.

Current lim red

Setting of the armature current limit, as % of Full load curr, when the Torque reduct

function is active.

Torque reduct

Selection for torque reduction. This function can be assigned to a freely programmable

digital input. When the torque reduction function is active, the current limit changes

accordingly by the percentage defined with the Current lim red parameter.

High

Torque reduction not active

Low

Torque reduction active