GEI-100332Ga

——— FUNCTION DESCRIPTION ———

6

122

Stop mode

OFF

The function is disabled.

Stop & Speed 0

The Start command determines the behavior. If the Start com-

mand is not present (digital or via terminal strip) and the drive is

stopped, the converter is blocked and the contact is open. When

the Start command is given, the converter is enabled and the

contact is closed. Disabling the Start command and after reaching

zero speed, the converter is blocked after a timespan set by Spd

0 trip delay. The relay contact between the terminals 75/76

opens after a timespan set by Trip cont delay.

Fast stp & spd 0

The Fast Stop command determines the behavior. If the Fast

Stop command is present (digital or via terminal strip; f.e. with

0 V on the terminal 14) and the drive is stopped, the converter is

blocked and the contact is open.When the Fast Stop command

is disabled (i.e. with 24 V on the terminal 14), The converter is

enabled and the contact is closed. Entering the Fast Stop com-

mand, when the zero speed has been reached, the converter is

blocked after a timespan set with Spd 0 trip delay.

Fst / stp & spd 0

The Fast Stop and Start commands determine the behavior. When

the Stop or Fast Stop commands are present and the drive is stopped,

the converter is blocked and the contact is open. When the Start

command is given or when the Fast Stop command is disabled, the

converter is blocked and the contact is closed. When the Start com-

mand is disabled or when a Fast Stop command is entered and after

reaching zero speed, the converter is stopped after a timespan set

by Spd 0 trip delay. The relay contact between the terminals

75/76 opens after a timespan set by Trip cont delay.

Spd 0 trip delay

Delay time in ms between reaching zero speed and disenabling of the converter.

Trip cont delay

Delay time in ms between disenabling and opening of the contact between the terminals

75 and 76.

Jog stop control

OFF

The behavior selected by Stop mode has no influence on the

Jog function.

ON

The behavior selected by Stop mode is active also on the Jog

function.

The mentioned “contact” can be either the one between the terminals 75/76 or a digital output (option TBO).

In both cases during the display of the message the “Stop control” parameter must be selected. The function

is factory set on the relay contact. The open contact, mentioned in the description, corresponds to 0 V on the

digital output, while the closed contact corresponds to +24 V on the digital output.

n

ote

!

At all the described possiblilities for Stop mode, the stop signal on the terminal 13 must be

present. With Main commands = Digital, it is necessary to select Enable drive parameter

= Enabled via keypad or Bus.