Direct mode: fhpp continuous mode – Festo Контроллеры двигателя SFC-LAC User Manual

Page 307

Advertising
background image

B. Parametrizing via field bus

B−87

Festo GDCP−SFC−LACI−DN−EN en 0812NH

Speed Limit

PNU

554

ć

uint32

rw

Description

Maximum permitted velocity with active force control.
In this way you can ensure that, if force control is activated by mistake
(e.g.Ăwork item missing), the axis will not undergo uncontrolled acceleration
and move at high speed against a stop.
This parameter is taken into account in all control modes in which the position
controller is not active in the status Operation enabled".

CI

60F6h

0

2h

uint32

rw

DeviceNet

C: 105

Aā: 54

I: 1

uint32

rw

Direct mode: FHPP Continuous Mode

Interpolation Time

PNU

570

ć

uint16

rw

Description

Time gap between two position specifications in FHPP Continuous Mode"
inĂ[

1

/

10

ms].

Value range: 0 ... 65535
See section 5.6.7

CI

20B6h

00h

uint16

rw

DeviceNet

C: 103

Aā: 48

I: 1

uint16

rw