B. Parametrizing via field bus

B−53

Festo GDCP−SFC−LACI−DN−EN en 0812NH

Extended Device Errors A

PNU

207

ć

uint16

rw

Description

Reading or deleting the active device fault(s)
Explanations of the error messages can be found in chapter 6.3 Diagnosis"

Writing <0>:

Delete all error messages (in 2FF1h, 2FFAh, 2FFBh and 2FFCh)

Read:
Bit 0 = 1:

Field bus fault (configuration of the parameters)

Bit 1 = 1:

Double MAC address recognized

Bit 2 = 1:

Receive queue overrun

Bit 3 = 1:

Transmit queue overrun

Bit 4 = 1:

CAN bus off, complete bus failed

Bit 5 = 1:

CAN controller queue overrun

Bit 6 = 0:

DeviceNet is reset

Bit 7 = 0:

Faulty bus supply

CI

2FFAh

00h

uint16

rw

DeviceNet

C: 108

Aā: 10

I: 1

uint16

rw

Extended Device Errors B

PNU

208

ć

uint16

rw

Description

Reading or deleting the active device fault(s)
Explanations of the error messages can be found in chapter 6.3 Diagnosis"

Writing <0>:

Delete all error messages (in 2FF1h, 2FFAh, 2FFBh and 2FFCh)

Read:
Bit 0:

ERROR INTERPOLATION CYCLE TIME (with FHPP continuous mode:
missing position specification, missing toggle bit)

Bit 1:

OVERCURRENT POWER STAGE

Bit 2:

LIMIT SWITCH ACTIVATED

Bit 3:

BLOCK DURING JOG MODE

CI

2FFBh

00h

uint16

rw

DeviceNet

C: 108

Aā: 11

I: 1

uint16

rw