Festo Контроллеры двигателя SFC-LAC User Manual

Page 31

Advertising
background image

1. System summary

1−9

Festo GDCP−SFC−LACI−DN−EN en 0812NH

Warning
There is no plausibility check to see whether the
deceleration (braking) that is set is actually achievable.
The deceleration that can be achieved depends on your
application (e.g.Ăpower and switching speed of your power
supply unit, effective load, mounting position).

If the deceleration cannot be achieved, an error will occur
and the controller may be turned off (depending on the
error). The effective load on the drive will continue to move
due to inertia, or it will fall if mounted in a vertical or
sloping position.

·

Perform a test run to see whether the quick stop
deceleration that is set is actually achievable.

·

When doing this, pay attention to the FCT diagram
(Measured data" page).

If the desired deceleration cannot be achieved:

·

Use stronger power units or reduce the dynamics.