5. Commissioning

5−10

Festo GDCP−SFC−LACI−DN−EN en 0812NH

Station number (MAC ID)

ć

Permitted station numbers: 0 ... 63

ć

An invalid station number is preset (shown on control
panel as ???").
This is to make sure that a correct address is set during
commissioning or exchange.

Baudrate (baud rate)

ć

Possible baud rates: 125, 250, 500 kBd

ć

An invalid baud rate is preset (shown on control panel as
???").
This is to make sure that a correct baud is set during
commissioning or exchange.

I/O Datalength (data length)

ć

The following settings are possible:

ć

8 bytes:
FHPP standard (control of the SFC−LACI takes place
according to Festo Handling and Positioning Profile)

ć

16 bytes:
FHPP standard and FHPP−FPC (additional use of the
FPC for parameterising the SFC−LACI). It is transmitted
in 3 telegrams.

ć

An invalid data length is preset (displayed as ???" on the
control panel). This is to make sure that the correct data
length is set during commissioning or exchange.

} Settings

BUS parameter

MAC ID

DeviceNet MAC ID

06 dec, 06 hex

ESC <Menu>

<––>

OK <Enter>

} Settings

BUS

parameter

Baudrate

BUS Baudrate

125 kBd

ESC <Menu>

<––>

OK <Enter>

} Settings

BUS parameter

I/O Datalength

I/O Datalength

08 byte

ESC <Menu>

<––>

OK <Enter>