5.6.8

Standstill monitoring

With the standstill monitoring it is clear that the target
position window is exited at a standstill.

When the target position has been reached and MC is
signalled in the status word, the drive switches to the
standstill" state and bit SPOS.B6 STILL (standstill monitor) is
reset. If, in this status, the drive is removed from the standstill
position window for a defined time due to external forces or
other influences, the bit SPOS.B6 STILL will be set.

As soon as the drive is in the standstill position window again
for the standstill monitoring time, the bit SPOS.B6 STILL is
reset.

1

Target position

2

Actual position

3

Standstill monitoring
(SPOS.B6)

4

Motion Complete
(SPOS.B2)

5

Standstill position
window

6

Target position
window

7

Damping time
(Position window
time)

8

Standstill monitoring
time

1

0

1

0

1

2

3

4

5 6

7

8

8

Fig. 5/8:

Standstill monitoring

Standstill monitoring becomes inactive when the standstill
position window is set to 0".