1 set the field bus parameter, Set the field bus parameter – Festo Контроллеры двигателя SFC-LAC User Manual

Page 113

Advertising
background image

5. Commissioning

5−9

Festo GDCP−SFC−LACI−DN−EN en 0812NH

5.2.1

Set the field bus parameter

·

Switch the SFC−LACI on. During first commissioning or
when the EEPROM has been deleted, the error message
DeviceNet INIT PARAMETER ERROR" will appear.

In order to set the field bus parameters during first
commissioning or after deletion of the EEPROM:

·

Select Config <Enter>.

For modifying the field bus parameters when re−commisioning
(i.e. when these parameters have already been completely
parameterised once):

·

Select [Settings] [BUS parameter] [...]
(see also section 4.5).

1. Select the desired field bus parameter with the arrow

keys (details see next page).

2. Press <Enter> to display the current setting.

3. If necessary, modify the setting with the arrow keys.

4. Accept the setting with OK <Enter>. The setting is saved

against network failure.

Note
The set field bus parameters first become effctive after
Power off/on" or after a software reset
(object 20F1/03h / PNU 127).

DeviceNet INIT
PARAMETER ERROR

Diagnostic <menu>

Config <Enter>

SFC–LACI...
D...
Xa = 0.00 mm

HMI:off
<Menu>

DeviceNet

MAC ID
Baudrate
I/O Datalength

ESC <Menu>

<–>

OK <Enter>

Advertising