5. Commissioning

5−81

Festo GDCP−SFC−LACI−DN−EN en 0812NH

Parameter / Description

CI

FCT

PNU

Out1: Value for setting condition
The saved value that when reached means that the comparison condition
is considered fulfilled in accordance with 2421/02h.
With record number comparison: bit number

Z record number:

bit 1 = record 1 (bit 0: do not use).
Example: 0x6 = in record1 and also in record2, the condition is

considered fulfilled and the output is set.

1243

x

2421/04h

Out1: Value for resetting condition
As above, but in accordance with 2421/03h for the resetting condition.

1244

x

2421/05h

Out1: Setting condition rising/falling
Value = 0: The output is set if the reference value accrued from lower

values has been reached in accordance with 2421/04h.

Value = 1: The output is set if the reference value accrued from higher

values has been reached in accordance with 2421/04h.

1245

x

2421/06h

Out1: Resetting condition rising/falling
Value = 0: The output is reset if the reference value accrued from lower

values has been reached in accordance with 2421/05h.

Value = 1: The output is reset if the reference value accrued from higher

values has been reached in accordance with 2421/05h.

1246

x

2421/07h

Out1: Delay
Delay time in [ms] after a resetting condition has occurred. The output is
not reset until the delay time has expired (= switch−off delay).

1247

x

2421/08h

Out1: Inverted
0 = not inverted
1 = inverted
This setting is not taken into account when the output is used for a
brake/clamping unit (see 2421/01h).

1248

x

2421/09h