B.2.4 example of parameterising via fpc, B.2.4, Example of parameterising via fpc – Festo Контроллеры двигателя SFC-LAC User Manual

Page 242: B−22

Advertising
background image

B. Parametrizing via field bus

B−22

Festo GDCP−SFC−LACI−DN−EN en 0812NH

B.2.4

Example of parameterising via FPC

A record in the position set table can be parameterised via
FPC in the following manner:

Step 1

Output status of the 8 bytes of FPC data:

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

Reserved Subindex ReqID/ResID + PNU

Parameter value

O data

0x00

0x00

0x

00

0x00

0x00

0x00

0x00

0x00

I data

0x00

0x00

0x

00

0x00

0x00

0x00

0x00

0x00

Step 2

write record number 1 with absolute positioning:
PNU 401, subindex 2 ć Modify parameter value, array, byte:
ReqID 12 (0xC) with value 0x00

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

Reserved Subindex ReqID/ResID + PNU

Parameter value

O data

0x00

0x

02

0x

C1

0x

91

Unused

Unused

Unused

0x

00

I data

0x00

0x

02

0x

C1

0x

91

0x00

0x00

0x00

0x

00

Step 3

After receiving the input data with ResID 0xC send output
data with ReqID = 0x0 and wait for input data with ResID =
0x0:

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

Reserved Subindex ReqID/ResID + PNU

Parameter value

O data

0x00

0x02

0x

01

0x91

Unused

Unused

Unused

0x00

I data

0x00

0x02

0x

01

0x91

0x00

0x00

0x00

0x00