5. Commissioning

5−39

Festo GDCP−SFC−LACI−DN−EN en 0812NH

5.5.6

Description of the status bytes SCON, SPOS, SDIR (RSB)

Status byte 1 (SCON)

Bit

EN

Description

B0
ENABLED

Drive

Enabled

= 0: Drive blocked, controller not active
= 1: Drive (controller) enabled

B1
OPEN

Operation Enabled

= 0: STOP active
= 1: Operation enabled, positioning possible

B2
WARN

Warning

= 0: Warning not applied
= 1: Warning applied

Fault number in diagnostic memory

B3
FAULT

Fault

= 0: No error
= 1: An error exists or an error reaction is active

Fault number in diagnostic memory

B4
24VL

Voltage Load

= 0: No load voltage
= 1: Load voltage applied

B5
HMI

Drive control

= 0: Device control by PLC/field bus
= 1: Device control by FCT/MMI

B6
OPM1

Operating Mode

= 00: Record select (standard)
= 01: Direct mode

10 reserved

B7
OPM2

= 10: reserved
= 11: reserved