5. Commissioning
5−27
Festo GDCP−SFC−LACI−DN−EN en 0812NH
5.4
Commissioning on a DeviceNet master
The following sections detail the configuration and
addressing of the SFC−LACI on a DeviceNet interface and a
DeviceNet master. To understand this section, you should be
familiar with DeviceNet and know the specification.
5.4.1
Overview of commissioning on the field bus
The following steps are required for commissioning the
SFC−LACI as a field bus participant:
1. Set the following on the SFC−LACI:
Settings
Description
MAC ID
Permitted address range: 0 ... 63
Baudrate
Permitted: 125 / 250 / 500 kBd
I/O Datalength
I/O data length
Ĉ 8 bytes (FHPP standard)
Ĉ 16 bytes (FHPP standard + FHPP−FPC)
·
on the control panel (only with type SFC−LACI−...−H2),
see section 4.5.6 and 5.2.1 or
·
with the Festo Configuration Tool (see help for the
Festo Configuration Tool).
2. Configure the master (section 5.4.2):
ć
install the EDS file,
ć
or make settings manually.
3. Test the field bus connection.