3.8

Bus termination with terminating resistors

Note
If the SFC−LACI is at the start or end of the field bus
segment, a bus terminator is required.

·

Always use a bus termination at both ends of the
fieldĂbus.

If you are using T−adapters, install the terminating resistor at
the unused output of the T−adapter.

Recommendation: Fit a terminating resistor in the Festo field
bus plug for the bus termination.

1

Protective cover

2

Resistor for bus
termination
(120 ġ, 0.25 W)

V+

GND

H

L

SLD

V+

GND

H

L

SLD

V+

GN
D

H

L

SLD

1

2

Fig. 3/7:

Bus termination with resistor in field bus plug FBS−SUB−9−BU−2x5POL−B

Field bus plug FBS−SUB−9−WS−CO−K (IP20) has an integrated
switchable terminating resistor.

Install a terminating resistor using the adapters

If the SFC−LACI you are connecting is at the end of the field
bus, you must install a terminating resistor (120 ġ, 0.25 W) in
the field bus socket:

·

Connect the terminating resistor between the cores for
CAN_H and CAN_L.